You are here

High Impedance Faults Modeling in Electrical Power Distribution Networks

Journal Name:

Publication Year:

Abstract (2. Language): 
High impedance fault (HIF) is an undesirable electrical contact between an energized conductor and a non-conducting object such as tree limbs, concrete walls and different ground surfaces. Besides public hazards, HIF increases power dissipation and may endanger network equipment. Detection of this fault by common protective devices existing in electrical power distribution systems is particularly difficult, because its occurrence causes only a small increase in load current which is usually below the detection level of such protective devices. Thus, conventional over-current protective devices cannot reliably detect HIFs. Although various protection schemes and detectors have been proposed to confront this fault, HIF detection is still remains an unsolved problem in power distribution level. The scope of this paper is to find a more accurate HIF modeling in order to achieve a better approximation of power system transient response in its faulted state, which is dramatically useful in developing or improving HIF detection algorithms and equipment. In this paper, a HIF arises from falling a tree on a medium voltage distribution network conductor is accurately modeled by two series time-varying resistors in EMTP/EMTP Works. Eventually, the simulation results of the proposed HIF model are compared with experimental results in order to examine the validity and accuracy of the proposed model.
FULL TEXT (PDF): 
38-42

REFERENCES

References: 

[1] PSRC Working Group D15, “High Impedance Fault Detection Technology”, Report of PSRC. March 1996, online available at: http://grouper.ieee.org/groups/td/dist/documents/highz.pdf.
[2] R. E. Lee, M. T. Bishop, "A comparison of measured high impedance fault data to digital computer modeling results", IEEE Transaction on Power Apparatus and System, Vol. PAS-104, No. 10, pp. 2754-2758, October 1985.
[3] A. E. Emanual, E. M. Gulachenski, D. Cyganski, J. A. Orr, S. Shiller, "High impedance fault arcing on sandy soil in 15 kV distribution feeders: contributions to the evaluation of the low frequency spectrum", IEEE Transaction on Power Delivery, Vol. PWRD-5, No. 2, pp. 676-683, April 1990.
[4] D. Wai and X. Yibin, “A Novel Technique for High Impedance Fault Identification”, IEEE Transactions on Power delivery, Vol. 13, No. 3, pp. 738-744, July 1998.
[5] N. Zamanan and J. K. Sykulski, “Modeling arcing high impedances faults in relation to the physical process in the electric arc”, WSEAS Transactions on Power Systems, pp. 28-33, 2006.
[6] S. R. Samantaray and P. K. Dash, “High Impedance Fault Detection in Distribution Feeders using Extended Kalman Filter and Support Vector Machine”, Euro. Trans. Electr. Power, 2010.
[7] S. R. Nam, J. K. Park, Y. C. Kang, and T. H. Kim, “A modeling method of high impedance fault in a distribution system using two series time varying resistances in EMTP”, IEEE PES Summer Meeting 2001, pp. 1175-1180, vol. 2, July 2001.
[8] N. I. Elkalashy, M. Lehtonen, H. A. Darwish, M. A. Izzularab and A-M. I. Taalab, "Modeling and Experimental Verification of High Impedance Arcing Fault in Medium Voltage Networks", IEEE Transactions on Dielectric and Electric Insulation, vol. 14, no. 2, pp. 375- 383, April 2007.
[9] H. A. Darwish and N. I. Elkalashy, “Universal Arc Representation Using EMTP”, IEEE Transactions on Power Delivery, vol. 2, no. 2, pp. 774-779, April 2005.
[10] A. Cassie, “Theorie Nouvelle des Arcs de Rupture et de la Rigidité des Circuits (Arc Rupture and Circuit Severity: A New Theory)”, Cigre Report 102, pp. 588-608, 1939.
[11] O. Mayr, “Beitrage zur Theorie des Statischen und des Dynamischen Lichthogens”, Archiv für Elektrotechnik (Electrical Engineering), Vol. Band 37, No. 12, pp. 588-608, 1943.
[12] M. Kizilcay and T. Pniok, “Digital Simulation of Fault Arcs in Power systems”, Europe Trans. Electr. Power Syst., ETEP, Vol. 4, pp. 55-59, 1991.

Thank you for copying data from http://www.arastirmax.com