You are here

İKİ KATMANLI TOPRAK MODELİNDE GENETİK ALGORİTMALAR İLE TOPRAKLAMA ÇUBUKLU VE ÇUBUKSUZ AĞ TASARIMI

DESIGN OF GROUNDING GRID WITH AND WITHOUT GROUNDING ROD IN TWO-LAYER SOIL MODEL VIA GENETIC ALGORITHMS

Journal Name:

Publication Year:

Author NameUniversity of AuthorFaculty of Author
Abstract (2. Language): 
Limiting Grounding Potential Rise(GPR) that may have a vital hazard for alives forms the basic of a safe grounding grid. In this paper, Genetic Algorithms(GA) method is proposed for the design of grounding grid on the structures of two-layer soil model and grid designs with and without grounding rods that are made by this method are compared. We have aimed both minimum cost and GPR is less than maximum allowable touch voltage on grounding grid designs. It is shown that grounding grid which are fast, cheap, easy, near to real, consistent and provides the safety conditions can be designed both with rods without rods by the way of purposed approach and the method. The role of grounding rods that carry out working safety conditions at grid designs is determined by cost analysis. Besides, the ground resistance that is measured on actual power system and the ground resistances that are calculated by uniform and two-layer soil models are compared.
Abstract (Original Language): 
Canlılar için hayati tehlike oluşturabilecek toprak potansiyel yükselmesi(GPR)’ nin sınırlandırılması güvenli bir topraklama şebekesinin temelini oluşturur. Bu çalışmada, iki katmanlı toprak modeli yapılarında güvenli bir topraklama ağı tasarımı için Genetik Algoritmalar(GA) metodu önerilmiş ve bu metod ile yapılan topraklama çubuklu ve çubuksuz ağ tasarımları karşılaştırılmıştır. Topraklama ağı tasarımlarında hem GPR’ nin müsaade edilebilir maksimum dokunma gerilimi(Edokunma)’ nden küçük olması esası hem de minimum maliyet hedeflenmiştir. Önerilen yaklaşım ve metod ile kolay, hızlı, tutarlı, düşük maliyetli, gerçeğe yakın ve emniyetli koşulları sağlayacak şekilde hem çubuklu hem de çubuksuz ağ tasarlanabileceği gösterilmiştir. Ağ tasarımlarında topraklama çubuklarının güvenli çalışma koşullarını yerine getirmesindeki rolü, maliyet analizi yapılarak belirlenmiştir. Ayrıca gerçek bir güç sistemi üzerinde ölçülen topraklama direnci ile, uniform ve iki katmanlı toprak modelleri ile hesaplanan topraklama direnci değerlerinin karşılaştırması da yapılmıştır.
247-266

REFERENCES

References: 

[1] Mürtezaoğlu K., “Yüksek Gerilim İstasyonlarında Topraklama Sistemi”, Yüksek Lisans
Tezi, İTÜ Fen Bilimleri Enstitüsü, 1998.
[2] Gürsu B., İnce M.C., “Genetik Algoritmalar İle Yüksek Gerilim İstasyonlarında Optimum
Topraklama Ağı Tasarımı”, Fen ve Mühendislik Bilimleri Dergisi, Fırat Üniversitesi,
Cilt:19, Sayı:4, 2007.
[3] Otero A.F., Cidras J., Garrido C., “Genetic Algorithm Based Method for Grounding Grid
Design”, IEEE International Conference on Evolutionary Computation Proceedings, 120-
123, 1998.
[4] Thasananutariya T.,Spuntupong K.,Chatratana S.,“Design of Grounding System for GIS
Indoor Substation”,TENCON 2004,IEEE Region 10 Conference,Vol.3,413-416, 2004.
[5] Costa M.C., Filho M.L.P., Marechal Y., Coulomb J.C., Cardoso J.R., “Optimization of
Grounding Grids by Response Surfaces and Genetic Algorithms”, IEEE Transaction on
Magnetics, Vol.39, No.3, 1301-1304, 2003.
[6] Neri F., “A New Evolutionary Method for Designing Grounding Grids by Touch Voltage
Control”, IEEE International Symposium on Industrial Electronics, Vol.2, 1501-1505,
2004.
[7] Covitti A., Delvecchio G., Fusco A., Lerario F., Neri F., “Two Cascade Genetic
Algorithms to Optimize Unequally Spaced Grounding Grids With Rods”, IEEE Eurocon,
1533-1536, 2005.
[8] IEEE Std.80-2000, IEEE Guide for Safety in AC Substation Grounding.
[9] Salama M.M.A., Elsherbiny M.M., Chow Y.L., “A Formula for Resistance of Substation
Grounding Grid in Two-Layer Soil”, IEEE Transactions on Power Delivery, Vol.10,
No.3, 1255-1262, 1995.
[10] Chow Y.L., Elsherbiny M.M., Salama M.M.A., “Resistance Formulas of Grounding
Systems in Two-Layer Earth”, IEEE Transactions on Power Delivery, Vol.11, No.3,
1330-1336, 1996.
[11] Nahman J.M., Djordjevic V.B., “Resistance to Ground of Combined Grid-Multiple Rods
Electrodes”, IEEE Transactions on Power Delivery,Vol.11,No.3,1337-1342, 1996.
[12] Elsherbiny M., “Simple Formulas for Calculating the Grounding Resistance of Rodbed
Buried in Non-Uniform Soil”, IEEE Proceedings of the 37th Midwest Symposium on
Circuits and Systems, Vol. 2, 1281-1284, 1995.
[13] Hocaoğlu M.H., Hocaoğlu A.T., “Yüksek Gerilim Tesisleri Topraklama Standartlarının
Karşılaştırılması”, Kaynak Elektrik Uluslararası Enerji Elektrik Elektronik ve Otomasyon
Dergisi, sayı: 134, 131-142, 2000.
[14] Öztürk O.İ., Kalenderli Ö.,“Topraklayıcılarda Potansiyel Dağılımının İki ve Üç Boyutlu
Sayısal Analizi”, İTÜ Dergisi/d Mühendislik, Cilt:5, Sayı:2,Kısım:1, 37-48, 2006.
[15] Chang C., Lee C.H., “Computation of Ground Resistances and Assesment of Ground Grid
Safety at 161/23.9 kV Indoor-Type Substation”, IEEE Transactions on Power Delivery,
Vol.21, No.3, 1250-1260, 2006.
[16] Katipoğulları O., “Karmaşık Topraklama Sistemlerinde Topraklama Empedansının
Ölçülmesi”, Gebze Yüksek Teknoloji Enstitüsü, Yüksek Lisans Tezi, 2003.

Thank you for copying data from http://www.arastirmax.com