Buradasınız

OPTİK FİBERLİ DAĞINIK ALGILAMA YÖNTEMİYLE ENERJİ KABLOSUNDA SICAKLIK VE GERGİNLİĞİN ALGILANMASI

Temperature and Strain Sensing by the Method of Optical Fiber Distributed Sensing in Power Cable

Journal Name:

Publication Year:

Abstract (2. Language): 
The cable insulation is exposed to electrical, thermal and mechanical effects during operation in XLPE insulated underground power cables. One of the important effects that the cable insulation is exposed is the maximum operation temperature and the other is the strain occurred on the insulation. In this study; temperature and strain sensing simulations have been performed along the 380 kV power cable by using a 1550 nm single mode fiber. Distributed temperature sensing method based on Raman scattering has been used to obtain temperature data along the cable. In order to obtain strain data along the cable, Brillouin frequency shift information of the back scattered signal has been utilized. Under the existence of simulation conditions such as cable connection points, cross-connection points and passing through ducts, temperature and strain profiles have been obtained along a 5 km cable with a spatial resolution of 1.5 m, a temperature resolution of ~ 1.25 ºC and a strain resolution of ~ 50 με by using Matlab 6.5. Furthermore, RMS noises detected on frequency shift and Brillouin power change have been computed as ~ 1.20 MHz and as ~ 0.45 % respectively by taking advantage of Brillouin frequency shift and the Brillouin power change profiles along the cable.
Abstract (Original Language): 
XLPE (çapraz bağlı polietilen) yalıtkanlı yüksek gerilim kablolarında, kablo yalıtkanı, çalışma esnasında elektriksel, ısıl ve mekanik etkilere maruz kalır. Kablo yalıtkanının maruz kaldığı önemli etkilerden biri maksimum işletme sıcaklığı, diğeri de yalıtkan üzerinde meydana gelen gerginliktir. Bu çalışmada, 1550 nm'de tek modlu optik fiber kullanılarak 380 kV yüksek gerilim kablosunda kablo boyunca sıcaklık ve gerginlik algılama benzetimleri yapılmıştır. Kablo boyunca sıcaklık verilerine ulaşabilmek için, Raman saçılmasını baz alan dağınık sıcaklık algılama yöntemi kullanılmıştır. Kablo boyunca gerginlik verilerinin elde edilebilmesi için de, geri saçılan işaretin Brillouin frekans kayması bilgisinden faydalanılmıştır. Kablo ek yerleri, kesişim noktaları ve boru içinden geçme gibi benzetim koşulları altında ve Matlab 6.5 programı kullanılarak 5 km uzunluklu kablo boyunca sıcaklık ve gerginlik profilleri 1.5 m uzamsal çözünürlükte, ~ 1.25 ºC sıcaklık çözünürlüğü ve ~ 50 με gerginlik çözünürlüğü ile elde edilmiştir. Ayrıca, kablo boyunca Brillouin frekans kayması ve Brillouin güç değişimi profillerinden faydalanılarak, frekans kayması üzerindeki etkin değer (RMS) gürültüsü ~ 1.20 MHz ve güç değişimi üzerindeki RMS gürültüsü ~ % 0.45 olarak hesaplanmıştır.
43-52

REFERENCES

References: 

1. Alahbabi M. N. (2005) Distributed Optical Fiber Sensors Based on the Coherent Detection of Spontaneous
Brillouin Scattering, Doktora Tezi, University of Southampton, Southampton, U.K.
2. Farahani, M. A., Gogolla, T. (1999) Spontaneous Raman Scattering in Optical Fibers with Modulated Probe Light
for Distributed Temperature Raman Remote Sensing, J. Lightwave Technol., 17(8), 1379-1391.
3. Garrido, C., Otero, A. F., Cidras, J. (2003) Theoretical Model to Calculate Steady-state and Transient Ampacity
and Temperature in Buried Cables, IEEE Trans. Power Delivery, 18(3), 667-678.
4. Geng, J., Xu, J., Li, Y., Wei, G., Guo, C. (2002) The Development of the Model and Arithmetic for the Fully
Distributed Fiber Optic Sensor Based on Raman Optical-fiber Frequency-domain Reflectometry, Sensors and
Actuators A: Physical, 101(1), 132-136.
5. Günday A. (2007) Enerji Kablosunda Oluşan Sıcaklık ve Gerilmeleri Optik Fiberli Algılayıcılarla Algılama Benzetimleri,
Yüksek Lisans Tezi, Uludağ Üniversitesi Fen Bilimleri Enstitüsü, Bursa.
6. Kee H. H., Lees G. P., Newson T. P. (2001) Simultaneous Independent Strain and Temperature Measurements
Over 15 km using Spontaneous Brillouin Scattering, ISAP 2000, Glasgow, U. K., 1-9.
7. Maughan S. M., Kee H. H., Newson T. P. (2001) Simultaneous Distributed Fiber Temperature and Strain Sensor
Using Microwave Coherent Detection of Spontaneous Brillouin Backscatter, Measurement Science and
Technology, 12(7), 834-842.
8. Nakamura S., Morooka S., Kawasaki K. (1992) Conductor Temperature Monitoring System in Underground
Power Transmission XLPE Cable Joints, IEEE Trans. Power Delivery, 7(4), 1688-1697.
9. Souza, P. D. (1999) Fiber Optic Distributed Sensing Based on Spontaneous Brillouin Scattering, Doktora Tezi,
University of Southampton, Southampton, U. K.
10. Yılmaz G., Karlık S. E. (2006) A Distributed Optical Fiber Sensor for Temperature Detection in Power Cables,
Sensors and Actuators A: Physical, 125(2), 148-155.

Thank you for copying data from http://www.arastirmax.com