THEORETICAL INVESTIGATION OF VAPOR COMPRESSION COOLING
CYCLE USING HFO-1234yf and HFO-1234ze
Journal Name:
- Gazi Üniversitesi Mühendislik-Mimarlık Fakültesi Dergisi
Keywords (Original Language):
Author Name | University of Author | Faculty of Author |
---|---|---|
Abstract (2. Language):
In this study, effects of using HFO-1234yf and HFO-1234ze recommended as an alternative refrigerant on cycle
performance and exergetic efficiency are presented. Because of HFO-1234yf and HFO-1234ze are suggested as
alternatives of HFC-134a, the cycle performance and cycle exergetic efficiency parameters are presented
comparatively for the refrigerants at the same working conditions and the same cycle. The effects of refrigerant
changing process are discussed. It was concluded that from the results, the cycle performance and exergetic
efficiency are almost same for HFC-134a and HFO-1234ze and higher than to HFO-1234yf. The difference
between these values is 15% for 50 oC condensing temperature.
Bookmark/Search this post with
Abstract (Original Language):
Bu çalışmada, alternatif soğutucu akışkanlar olarak günümüzde ön plana çıkan, HFO-1234yf ve HFO-
1234ze’nin, bir buhar sıkıştırmalı mekanik soğutma çevriminin etkinliğine ve ekserji verimine olan etkileri
teorik olarak incelenmiştir. HFO-1234yf ve HFO-1234ze soğutkanları, HFC-134a soğutucu akışkanlarına
alternatif olarak önerildiği için bu üç akışkanın, aynı çevrim ve çalışma aralıklarında, çevrim etkinliğine ve
çevrimin ekserji verimine etkileri karşılaştırmalı olarak sunulmuştur ve bu akışkan değişikliklerinin etkileri
tartışılmıştır. Sonuçlar göstermektedir ki, HFC-134a ve HFO-1234ze soğutkanları ile elde edilen çevrim etkinliği
ve ekserji verimi değerleri, hemen hemen, aynıdır ve HFO-1234yf’nin kullanıldığı duruma oranla yüksektir. Bu
fark yoğuşturucu sıcaklığı 50 oC iken % 15 gibi yüksek bir değere çıkmıştır.