ABSORPSİYONLU SOĞUTMA SİSTEMLERİNDE KULLANILAN EŞANJÖRLERİN SİSTEMİN PERFORMANSINA ETKİSİ

Effect On Performance Of The Systems Of Heat Exchangers Used In Absorption Refrigeration Systems

Journal Name:

Publication Year:

Abstract (2. Language): 
In this study, the effect of heat exchangers, which are used to recovery heat energy in the absorption refrigeration systems, is investigated on the coefficient of performance (COP). Ammonia-water solution, widely used in the absorption refrigeration systems, is taken as an absorbent-refrigeration pair. Thermodynamic analysis of system is performed and thermodynamic properties of ammonia and ammonia-water solution are presented. The effect of effectiveness variations for three heat exchangers, which are used in the system, are observed on COP. Also, the effect of generator, evaporator, condenser and absorber temperatures are investigated on COP. As a result, the most effective heat exchanger on the system performance is solution heat exchanger. The system performance increases with increasing generator and evaporator temperatures, but decreases with increasing condenser and absorber temperatures.
Abstract (Original Language): 
Bu çalışmada, absorpsiyonlu soğutma sistemlerinde ısı geri kazanımı için kullanılan eşanjörlerin, sistemin performans katsayısına (COP) etkileri incelenmiştir. Sistemde kullanılan çift olarak, absorpsiyonlu soğutma sistemleri arasında yaygın kullanım alanı olan NH3-H2O eriyiği alınmıştır. Çevrimin termodinamik analizi yapılarak, amonyak ve amonyak-su eriyiğine ait termodinamik özellikler verilmiştir. Sistemde kullanılan 3 adet eşanjörün etkenlik katsayılarının değişiminin, sistemin COP değeri üzerindeki etkileri gözlenmiştir. Ayrıca, kaynatıcı, buharlaştırıcı, yoğuşturucu ve absorber sıcaklıklarının sistemin performansına etkileri araştırılmıştır. Sonuç olarak, sistemin performansına en fazla etkisi olan eşanjörün eriyik eşanjörü olduğu ve sistemin performansı, kaynatıcı ve buharlaştırıcı sıcaklıklarının artmasıyla artarken, yoğuşturucu ve absorber sıcaklıklarının artmasıyla azaldığı görülmüştür.
111-120

REFERENCES

References: 

1. ASHRAE, (1993). ASHRAE handbook – Fundamentals, chapter 1. Atlanta: American Society of
Heating, Refrigeration and Air-Conditioning Engineers. 34p.2. Horuz, İ. (1990) Absorpsiyonlu Soğutma Sistemlerinden Amonyak-Su Çifti İle Lityum Bromür-Su
Çiftinin Mukayesesi, Yüksek Lisans Tezi. Bursa. 147s.
3. Horuz, İ (1998) A comparison between ammonia-water and water-lithium bromide solutions in vapor
absorption refrigeration systems. Int. Comm. Heat and Mass Transfer, Vol. 25, No. 5, 711-721p.
4. Lazzarin, R.M., Gasparella, A., Longo, G.A. (1996) Ammonia-water absorption machines for
refrigeration: theoretical and real performances. International Journal of Refrigeration, Vol. 19, No. 4,
239-246p.
5. Mostafavi, M, Agnew, B. (1996) The impact of ambient temparature on lithium bromide-water
absorption machine performance. Applied Thermal Engineering, Vol. 16, No. 6, 515-522p.
6. Seara, J. F., Vazquez, M. (2001) Study and control optimal the generation temperature in NH3-H2O
absorption refrigeration systems. Applied Thermal Engineering, Vol. 21, 343-357p.
7. Stoecker, W.F., Jones, J.W. (1982) Refrigeration And Air Conditioning, McGraw-Hill International
Editions, Singapore. 328-350p.
8. Sun, D.W. (1998) Comparison of the performance of NH3-H2O, NH3-LiNO3 and NH3-NaSCN
absorption refrigeration systems. Energy Conversion, Vol. 39, No. 5/6, 357-368p.

Thank you for copying data from http://www.arastirmax.com